Product application:
BVR is applicable to AC rated voltage U0/U is 450/750V and below, daily electrical appliances, instruments, instrumentation telecommunications equipment and power line fixed laying lines.
Mainly used for fixed wiring when soft requirements are required.
Application standard:
GB/T8734.2.-2012
Product Features:
1. Long-term working temperature is allowed to not exceed 70℃
2. The temperature of cable laying cannot be lower than 0℃
3. Conductor is made of high quality oxygen-free copper wire, high conductivity, low loss
4. The insulation layer is made of high quality PVC, high strength, wear resistance and corrosion resistance.
5. Color optional: red, black, blue, green, yellow, yellow green
6. Packing length: 100m/roll, 200m/roll or as customers’ requires.
BVR 450/750Vcopper core PVC insulated flexible cable
Cores type×Standard section (mm2) |
Insulation thickness nominal value (mm) |
Average form factor (mm) Lower limit |
Maximum conductor resistance (Ω/km) |
Insulation resistance minimum at 70℃ (Ω/km) |
|
---|---|---|---|---|---|
Copper core | Tinned Copper core | ||||
0.75 | 0.7 | 2.9 | 24.5 | 24.8 | 0.013 |
1.0 | 0.7 | 3.1 | 18.1 | 18.2 | 0.012 |
1.5 | 0.7 | 3.4 | 12.1 | 12.2 | 0.011 |
2.5 | 0.8 | 4.1 | 7.41 | 7.56 | 0.011 |
4 | 0.8 | 4.8 | 4.61 | 4.7 | 0.009 |
6 | 0.8 | 5.3 | 3.08 | 3.11 | 0.0084 |
10 | 1.0 | 7.3 | 1.83 | 1.84 | 0.0072 |
16 | 1.0 | 8.6 | 1.15 | 1.16 | 0.0062 |
25 | 1.2 | 10.2 | 0.727 | 0.734 | 0.0058 |
35 | 1.2 | 11.7 | 0.524 | 0.529 | 0.0052 |
50 | 1.4 | 13.9 | 0.387 | 0.391 | 0.0051 |
70 | 1.4 | 16.0 | 0.268 | 0.270 | 0.0045 |